Input
Flow Input: 1 x Analogue (I) / Pulse
Temperature Input: 1 x RTD
Density Input: 1 x Analogue (I)
Loop Power Supply: 24V DC (+/-16%)
Output
Active Output: 1 x Analogue (I) / Pulse
Digital Outputs: 2 x Open Collector
Display
Type: 160 x 80 Dot-Matrix LCD with white backlight
Alarm Indication: Colour change during alarm events
Active Display Area: 70 x 34 mm
Calculations
Volume Calculation
Power Supply
Low Voltage Power Supply: 100 to 230 V AC (-15% / +10%)
Small Voltage Power Supply:
24 V DC (-50% / +75%)
24 V AC (±50%)
Dimensions
Size (WxHxD): 144 x 144 x 103.1 mm (5.67″ x 5.67″ x 4.06″)
Protection Class
IP65
Communication Interfaces
RS232
USB
Ethernet
Modbus TCP
Modbus RTU
Certificates
CE
CSA GP
NTEP (USA)
The Batch Controller RA33 is specifically designed for recording flow and controlling output signals for valves and pumps, ensuring precise dosing of predefined batch quantities. It features a temperature/density compensation function to correct the measured volume, optimizing filling processes with both automatic and fixed after-run corrections. It can accommodate the correction of mineral oils in accordance with the ASTM D1250-04 standard.
Typical Applications Include:
Accurate Results:
Fixed and automatic after-run corrections ensure constant, highly accurate dosing.
Enhanced Quality:
Enables fast and precise dosing to improve product quality.
Volume Correction:
Optional volume correction for mineral oils as per ASTM D1250-04 enhances measurement accuracy.
Detailed Logging:
Comprehensive logging of protocols, including preset counters, volume counters, batch names, numbers, error messages, and changes to operating parameters.
Standard Compatibility:
Compatible with common flow transmitters, temperature sensors, and density sensors.
Remote Control Options:
Capability to start and abort batch runs remotely.
Statistical Analysis:
Provides daily, monthly, and annual statistics on batch run sizes and quantities.
The Batch Controller RA33 functions as a Batch Controller, specifically designed for filling and dosing applications. It adheres to the ASTM D1250-04 calculation standards for precise volume measurement.